Forney MAXFiregas Igniter

120
  • Style:Forney 福尼MAXFiregas点火器
  • Specifications:Forney 福尼MAXFiregas点火器
  • Online ordering

Forney 福尼MAXFiregas点火器

在5种可用容量中的每一种都采用了“受保护的主燃烧区”设计。点火过程从导管内部开始,远离燃烧器环境,从而产生极其稳定可靠的点火器。容量(标称)范围为1 mmBtu/hr至50 mmBtu/hr。

MAXFiregas点火器为主火焰点火、火焰稳定和锅炉预热提供了最可靠的能源。

云联技术 支持 询价报价njxj888@163.com

The MAXFire 100 Series gas igniter incorporates the “protected primary combustion zone” design in each of the 5 capacities available. The ignition process starts inside the guide tube away from the burner environment resulting in an extremely stable and reliable igniter. Capacities (nominal) range from 1 mmBtu/hr to 50 mmBtu/hr.

Specifications

Fuel: Natural gas or propane
Minimum Length: 14 inches
Guide Tube Material: 10 & 30 – Stainless steel
35, 40 & 50 – Carbon steel with 12” stainless steel at furnace end

MAXFire
Model
Capacity
MBtu/hr
Guide
Tube OD
Connections (NPT)
Gas Air
Cooling Air
Requirement*
Nozzle
Type
Typical Fuel
Pressure (psig)
110 0.3 to 1.5 1 7/8” 1/2” 3/4” 23 @ 3 Straight 5-12
130 1.5 to 6.0 2 7/8” 3/4” 3/4” 45 @ 3 Straight or wide 5-12
135 5.0 to 15 3 1/2” 1 1/2” 1 1/2” 50 @ 6 Straight or wide 5-25
140 5.0 to 25 4” 1 1/2” 1 1/2” 80 @ 6 Straight or wide 5-25
150 10 to 50 5” TBD TBD 120 @ 6 Straight or wide 5-25

 

Contact Us

telephone:025-52791167,52791168

Fax:025-52791169

Phone :13390905858

mailbox:njxj888@163.com skype:yluedq