Forney 福尼 adVantage风管燃烧器Duct Burners
adVantage风管燃烧器在最具挑战性的条件下运行。优质组件和专利技术的结合,使其性能与其他管道燃烧器不同。
应用规范
管道横截面: 3至50英尺(0.91至15 25米)
热量输入: 10至1100百万英热单位/小时(2 .93至322兆瓦)
入口氧气水平:≥10.5%湿,不增加空气
入口H2O:≤20%, 不增加空气
燃烧器的TEG分布: 90%横截面上平均速度的+20%
adVantage Duct Burners perform in the most challenging conditions. Premium components and patented technology join to perform like no other duct burner.
Duct cross sections: 3 to 50 feet (0.91 to 15.25 meter)
Heat inputs: 10 to 1100 MMBtu/hr (2.93 to 322 MW)
Inlet oxygen levels: ≥ 10.5% wet without augmenting air
Inlet H2O: ≤ 20% without augmenting air
TEG distribution to the burner: ± 20% of the average velocity over 90% of the cross section
For most advanced gas turbine applications firing natural gas – assuming < 12% wet H2O; Firing Temperatures>1200°F (649°C), we offer the following emission guarantees in HHV over turndown – without augmenting air:
电话:025-52791167,52791168
传真:025-52791169
手机 :13390905858
邮箱:njxj888@163.com skype:yluedq